The issue :
The maximum existing lighting obtained is only about 100 lx, whereas the lux standard of the storage room based on company regulations is an average of at least 250 lx based on SNI 03-6197-2000.
Improvement:
Replace the number of lamp points and type of existing lamp with PHILIPS DN560B 1 xLED12S/830 M 13W 1430 lm for each room.Â
The average lux in the aisle area at a work plane height of 76 cm reaches 250 lx and this already meets the regulations.
Leadtime:
4 weeks (briefing, design and development, finalization and documentation)